{"id":19691,"date":"2021-07-16T09:00:00","date_gmt":"2021-07-16T08:00:00","guid":{"rendered":"https:\/\/www.engineernewsnetwork.com\/blog\/?p=19691"},"modified":"2021-07-15T09:53:01","modified_gmt":"2021-07-15T08:53:01","slug":"is-your-alarm-annunciator-networked-to-your-scada","status":"publish","type":"post","link":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/","title":{"rendered":"Is your alarm annunciator networked to your SCADA?"},"content":{"rendered":"\n<p><strong>Alarm annunciators have been around for decades. Initially hard-wired to critical processes, then for many years plants began networking alarms to their SCADA systems. Today, due to improved safety standards, they are back to being hard-wired. Both methods have their advantages, but hard-wiring alarm annunciators is more effective for plant safety. Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system\u00a0<\/strong><\/p>\n\n\n\n<p>The 1970s, 80s and early 90s saw a big market for the hardwired alarm annunciator. Most plants containing hazardous materials had all their alarms hardwired to alarm annunciator systems around the plant and &nbsp; back to the control room. These alarm annunciators would have a matrix of numerous alarm windows in panels that would light up and sound an audible alarm in the event of abnormal operating conditions. The issue was that only operators in the immediate vicinity of the alarm annunciator, would be alerted to the abnormal condition.&nbsp;<\/p>\n\n\n\n<p>The solution to this during the mid-1990s was to network all the alarms to the plant\u2019s SCADA system. This had the advantage of cost-effectively relaying the alarm to a safe control room, as well as logging the alarms and using this historical log for post-event analysis. <\/p>\n\n\n\n<p>However, notifications on the SCADA screen \u2014 when combined with other non-critical alarms\/events \u2014 were easier to miss and cause confusion to the operators resulting in response times suffering.\u00a0<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><a href=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-scaled.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"683\" src=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-1024x683.jpg\" alt=\"\" class=\"wp-image-19693\" srcset=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-1024x683.jpg 1024w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-300x200.jpg 300w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-768x512.jpg 768w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-1536x1024.jpg 1536w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-2-2048x1365.jpg 2048w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><\/a><figcaption>Alarm annunciators are nothing new, they have been around for decades<\/figcaption><\/figure>\n\n\n\n<p><strong>Today\u2019s alarm annunciators<\/strong><\/p>\n\n\n\n<p>The current IEC 61508 safety integrity levels are international standards by which most safety-critical systems are rated. It is understood that while zero risk can never be reached, only probabilities can be reduced, there are safety functions that can be put in place to ensure risk is minimised.\u00a0<\/p>\n\n\n\n<p>The modern-day approach to the use of alarm annunciators is to rationalise the number of alarm windows so that only the safety critical alarms are displayed on them. This makes it easier for the operator to take immediate action. There is now also the option to independently network the annunciator, wirelessly or via Ethernet, to the plant\u2019s SCADA system.<\/p>\n\n\n\n<p>By doing this, data from the annunciator is logged without compromising the safety function if the network connection were to be lost. This is possible by using Omniflex\u2019s Teleterm Unit, which simply connects to the alarm annunciator via a Modbus serial cable. These Teleterm units also provide a flexible interface to other process signals, allowing operators to remotely monitor and control other plant devices on their SCADA systems as well as the alarms.<\/p>\n\n\n\n<p>Teleterm units are designed to enable operators to communicate with a wide range of devices and machines. They can use GSM, Ethernet, RS232, RS485, Licence-free radio or even existing plant cabling up to distances of 10 km.&nbsp; They can also communicate directly with a plant\u2019s SCADA using Modbus TCP, OPC Servers or IoT web service.&nbsp;<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><a href=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-scaled.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"683\" src=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-1024x683.jpg\" alt=\"\" class=\"wp-image-19694\" srcset=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-1024x683.jpg 1024w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-300x200.jpg 300w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-768x512.jpg 768w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-1536x1024.jpg 1536w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/Gary-Bradshaw-Director-at-Omniflex-2048x1365.jpg 2048w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><\/a><figcaption>Gary Bradshaw, director of alarm annunciator specialist Omniflex<\/figcaption><\/figure>\n\n\n\n<p>Operator response times are an important part of the SIL-rating, so being notified early of any abnormal condition occurring is crucial. Teleterm units also make it possible to send out SMS alerts or emails to phones, tablets and PCs, which can be customised as to who receives certain alerts. This ensures the relevant personnel are aware of the problem and therefore maximises response times. \u00a0<\/p>\n\n\n\n<p>Omniflex manufactures a large range of teleterm interface units which can be selected depending on the customers application. &nbsp;<\/p>\n\n\n\n<p>Although alarm annunciators are back to being hard-wired, this doesn\u2019t mean plant operators have to lose out on the benefits of having annunciators networked to their SCADA system. Using a Teleterm unit means operators get the best of both worlds, without compromising the safety function of the alarm annunciator. &nbsp;<\/p>\n\n\n\n<p>Omniflex offers free site surveys in the UK advising on the best Alarm Annunciator solution either for a new installation or for the replacement of obsolete systems.\u00a0<\/p>\n\n\n\n<p>Gary Bradshaw is director of alarm annunciator specialist <strong><a href=\"https:\/\/www.omniflex.com\/solutions_legacy_alarm_annunciators.php?utm_source=Stone%20Junction&amp;utm_medium=blog%20post&amp;utm_campaign=OMN043%20-%20Networking%20annunciators%20-%20BP\" target=\"_blank\" rel=\"noreferrer noopener\">Omniflex<\/a><\/strong>. <\/p>\n","protected":false},"excerpt":{"rendered":"<p>Alarm annunciators have been around for decades. Initially hard-wired to critical processes, then for many years plants began networking alarms to their SCADA systems. Today, due to improved safety standards, they are back to being hard-wired. Both methods have their advantages, but hard-wiring alarm annunciators is more effective for plant safety. Gary Bradshaw, explains how &hellip;<\/p>\n","protected":false},"author":1,"featured_media":19692,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[1],"tags":[7734,7202],"class_list":["post-19691","post","type-post","status-publish","format-standard","has-post-thumbnail","","category-process","tag-alarm-annunciators","tag-omniflex"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.2 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Is your alarm annunciator networked to your SCADA? - Engineer News Network<\/title>\n<meta name=\"description\" content=\"Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Is your alarm annunciator networked to your SCADA? - Engineer News Network\" \/>\n<meta property=\"og:description\" content=\"Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\" \/>\n<meta property=\"og:site_name\" content=\"Engineer News Network\" \/>\n<meta property=\"article:published_time\" content=\"2021-07-16T08:00:00+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"2560\" \/>\n\t<meta property=\"og:image:height\" content=\"1707\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"admin\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"admin\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"4 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\"},\"author\":{\"name\":\"admin\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1\"},\"headline\":\"Is your alarm annunciator networked to your SCADA?\",\"datePublished\":\"2021-07-16T08:00:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\"},\"wordCount\":686,\"image\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg\",\"keywords\":[\"alarm annunciators\",\"Omniflex\"],\"articleSection\":[\"Process\"],\"inLanguage\":\"en-GB\"},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\",\"url\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\",\"name\":\"Is your alarm annunciator networked to your SCADA? - Engineer News Network\",\"isPartOf\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg\",\"datePublished\":\"2021-07-16T08:00:00+00:00\",\"author\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1\"},\"description\":\"Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system\",\"breadcrumb\":{\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage\",\"url\":\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg\",\"contentUrl\":\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg\",\"width\":2560,\"height\":1707,\"caption\":\"Alarm annunciators should be networked to a plant\u2019s SCADA system for optimised safety\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/www.engineernewsnetwork.com\/blog\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Is your alarm annunciator networked to your SCADA?\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/#website\",\"url\":\"https:\/\/www.engineernewsnetwork.com\/blog\/\",\"name\":\"Engineer News Network\",\"description\":\"The ultimate online news and information resource for today's engineer\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/www.engineernewsnetwork.com\/blog\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1\",\"name\":\"admin\",\"url\":\"https:\/\/www.engineernewsnetwork.com\/blog\/author\/admin\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Is your alarm annunciator networked to your SCADA? - Engineer News Network","description":"Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/","og_locale":"en_GB","og_type":"article","og_title":"Is your alarm annunciator networked to your SCADA? - Engineer News Network","og_description":"Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system","og_url":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/","og_site_name":"Engineer News Network","article_published_time":"2021-07-16T08:00:00+00:00","og_image":[{"width":2560,"height":1707,"url":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg","type":"image\/jpeg"}],"author":"admin","twitter_card":"summary_large_image","twitter_misc":{"Written by":"admin","Estimated reading time":"4 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#article","isPartOf":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/"},"author":{"name":"admin","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1"},"headline":"Is your alarm annunciator networked to your SCADA?","datePublished":"2021-07-16T08:00:00+00:00","mainEntityOfPage":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/"},"wordCount":686,"image":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage"},"thumbnailUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg","keywords":["alarm annunciators","Omniflex"],"articleSection":["Process"],"inLanguage":"en-GB"},{"@type":"WebPage","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/","url":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/","name":"Is your alarm annunciator networked to your SCADA? - Engineer News Network","isPartOf":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage"},"image":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage"},"thumbnailUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg","datePublished":"2021-07-16T08:00:00+00:00","author":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1"},"description":"Gary Bradshaw, explains how plant operators can have the best of both worlds by hard-wiring their critical systems to an annunciator and also networking them back to their SCADA system","breadcrumb":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/"]}]},{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#primaryimage","url":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg","contentUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2021\/07\/OMN043-Image-1-scaled.jpg","width":2560,"height":1707,"caption":"Alarm annunciators should be networked to a plant\u2019s SCADA system for optimised safety"},{"@type":"BreadcrumbList","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/is-your-alarm-annunciator-networked-to-your-scada\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.engineernewsnetwork.com\/blog\/"},{"@type":"ListItem","position":2,"name":"Is your alarm annunciator networked to your SCADA?"}]},{"@type":"WebSite","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#website","url":"https:\/\/www.engineernewsnetwork.com\/blog\/","name":"Engineer News Network","description":"The ultimate online news and information resource for today's engineer","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.engineernewsnetwork.com\/blog\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Person","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1","name":"admin","url":"https:\/\/www.engineernewsnetwork.com\/blog\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/19691","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/comments?post=19691"}],"version-history":[{"count":1,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/19691\/revisions"}],"predecessor-version":[{"id":19695,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/19691\/revisions\/19695"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/media\/19692"}],"wp:attachment":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/media?parent=19691"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/categories?post=19691"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/tags?post=19691"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}