{"id":31653,"date":"2026-03-24T09:45:00","date_gmt":"2026-03-24T09:45:00","guid":{"rendered":"https:\/\/www.engineernewsnetwork.com\/blog\/?p=31653"},"modified":"2026-03-24T14:48:34","modified_gmt":"2026-03-24T14:48:34","slug":"how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories","status":"publish","type":"post","link":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/","title":{"rendered":"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories"},"content":{"rendered":"\n<p><strong>With more than 100GW of new AI data centre capacity expected between 2026 and 2030, operators are discovering that traditional AC energy infrastructure can&#8217;t scale alongside megawatt\u2011class GPU racks. In AC power chains, 10-30% of all incoming energy is lost as heat before it ever reaches a GPU, an inefficiency many operators now call the&nbsp;conversion tax. The industry is rapidly moving toward 800\u20131500V DC power distribution because AI racks are outgrowing what traditional AC infrastructure can support. Dafna Granot, Meir Adest and Igor Morozov report<\/strong><\/p>\n\n\n\n<p>The rapid expansion of AI data centres is severely constrained by power generation and grid capacity. As operators prioritize maximizing usable compute per megawatt, legacy AC-powered infrastructure has become a critical bottleneck. Traditional AC-powered systems impose a &#8216;Conversion Tax&#8217;\u201d&#8217; &#8211; wasting an estimated 10\u201330% of input power through multiple conversion stages while struggling to handle the thermal and density demands of next-gen GPU racks approaching 1 MW each<a href=\"#_ftn1\" id=\"_ftnref1\">[1]<\/a>. To overcome these constraints, the industry is accelerating its transition toward 800V direct-current (DC) architectures to minimize cabling bulk, drastically reduce conversion losses, and enable unprecedented power densities.<\/p>\n\n\n\n<p>To navigate this transition, this paper introduces a five-stage maturity framework for data center power architectures, evolving from legacy AC setups (Stage 0) to an ultimate Integrated DC-native solution (Stage 4). This framework maps the industry\u2019s potential progression through intermediate retrofit and hybrid models, which incrementally reduce AC dependencies&nbsp; but still carry significant system complexity and conversion penalties. Ultimately, it demonstrates that maximizing compute density requires advancing past early DC-native designs (Stage 3) to a fully streamlined Stage 4 architecture.<\/p>\n\n\n\n<p>SolarEdge is engineering a holistic, Stage 4 power platform position to directly connect medium voltage (MV) lines to the DC bus. At its core is an ultra-high efficiency (&gt;99%) Solid State Transformer (SST), paired with a highly configurable native DC-UPS and an intelligent DC-power distribution layer. By eliminating redundant AC-DC-AC conversion cycles, step-down transformers, and separate low-voltage units, this integrated architecture is aimed to achieve a groundbreaking total system efficiency of up to 98%-reclaiming previously wasted power and transforming it into revenue-generating compute.<\/p>\n\n\n\n<p>Transitioning to an 800V DC architecture requires unparalleled expertise in high-voltage DC system design, real-time management, and massive operational scale. Drawing on two decades of leadership in power electronics, SolarEdge naturally adapts advanced distributed energy technologies to meet the rigorous safety and control demands of AI workloads. Backed by the real-time monitoring of millions of DC-coupled systems, over 140 million units deployed worldwide and operational track record of 60GW+, SolarEdge is uniquely positioned to deliver this highly efficient, gigawatt-scale infrastructure on time.<\/p>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-full is-resized\"><a href=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png\"><img loading=\"lazy\" decoding=\"async\" width=\"602\" height=\"245\" src=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png\" alt=\"\" class=\"wp-image-31654\" style=\"aspect-ratio:2.457392524556704;width:602px;height:auto\" srcset=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png 602w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-300x122.png 300w\" sizes=\"auto, (max-width: 602px) 100vw, 602px\" \/><\/a><figcaption class=\"wp-element-caption\">Data centre power infrastructure maturity stages<\/figcaption><\/figure>\n<\/div>\n\n\n<p><strong>Power delivery: the bottleneck of the AI data centres<\/strong><\/p>\n\n\n\n<p>The AI Boom is triggering an unprecedented infrastructure investment, with &gt;100GW of AI data centers expected to be built between 2026\u20132030<a href=\"#_ftn2\" id=\"_ftnref2\">[2]<\/a>. Generation and transmission constraints limit new data center buildout, with substantial power shortfall expected in coming years. As a result, grid connection capacity is increasingly the gating factor for data center expansion. This is pushing operators toward approaches such as on-site generation and more flexible interconnection\/contracting models. Still, the top priority remains maximising usable compute per megawatt of grid capacity.<\/p>\n\n\n\n<p>One of the most direct ways to improve compute utilisation is to reduce power conversion losses. In traditional AC power chains, electricity typically passes through 5\u20137 conversion stages from grid to GPU, with an estimated ~10\u201330% of input power lost as heat from generation to end use. In today\u2019s power-constrained environment, data center operators can no longer afford this &#8216;Conversion Tax \u2013a material penalty on both capacity (less power reaches IT load) and cost (more cooling and electrical infrastructure).<\/p>\n\n\n\n<p>In parallel, AI workloads are driving a sharp rise in rack power density as GPUs grow more power hungry and more tightly coupled. For example, NVIDIA\u2019s announced Kyber racks with Rubin Ultra GPUs are expected to approach ~1MW per rack\u2013a massive 25x leap over previous-generation standards. This rapid densification further stresses power delivery architecture and amplifies the value of higher-efficiency, lower-loss distribution.<\/p>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-full\"><a href=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-1.png\"><img loading=\"lazy\" decoding=\"async\" width=\"602\" height=\"203\" src=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-1.png\" alt=\"\" class=\"wp-image-31655\" srcset=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-1.png 602w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-1-300x101.png 300w\" sizes=\"auto, (max-width: 602px) 100vw, 602px\" \/><\/a><figcaption class=\"wp-element-caption\">Legacy AC data centre power conversion architecture<\/figcaption><\/figure>\n<\/div>\n\n\n<p><strong>The data centre power infrastructure transition<\/strong><\/p>\n\n\n\n<p>Legacy AC\u2011powered infrastructure is hitting a thermal and physical ceiling, unable to support next\u2011generation AI clusters. Much like liquid cooling transitioned from a premium offering to a physical requirement for 100kW racks, direct\u2011current (DC) distribution is becoming a necessity for megawatt\u2011scale deployments. The industry is converging on 800V DC architectures to minimise cabling bulk, drastically reduce conversion losses, and enable unprecedented power densities. While data centres typically interface with Medium Voltage (MV) AC lines (10kV\u201334.5kV), the path to 800V DC varies. Two primary emerging rack standards are NVIDIA\u2019s monopolar 800V DC end\u2011to\u2011end architecture and OCP\u2019s Mt. Diablo \u00b1400V DC specification.<\/p>\n\n\n\n<p>Strategies for the transition range from whitespace retrofits to hybrid configurations. However, DC\u2011native solutions are expected to ultimately prevail, offering superior efficiency, optimized whitespace utilization, and reduced CapEx.<\/p>\n\n\n\n<p>To facilitate the discussion, we propose a framework<a href=\"#_ftn3\" id=\"_ftnref3\">[3]<\/a> describing the evolution of data center power architecture from today\u2019s AC infrastructure to the ultimate DC\u2011native solution. Each stage of this evolution streamlines the power path, reducing component count while maximising efficiency gains and grid compatibility for high\u2011density AI clusters<a href=\"#_ftn4\" id=\"_ftnref4\">[4]<\/a>.<\/p>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-full\"><a href=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-3.png\"><img loading=\"lazy\" decoding=\"async\" width=\"602\" height=\"333\" src=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-3.png\" alt=\"\" class=\"wp-image-31657\" srcset=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-3.png 602w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-3-300x166.png 300w\" sizes=\"auto, (max-width: 602px) 100vw, 602px\" \/><\/a><figcaption class=\"wp-element-caption\">Data centre power infrastructure maturity stages<\/figcaption><\/figure>\n<\/div>\n\n\n<p><strong>Stage 0: AC infrastructure (current state):<\/strong><\/p>\n\n\n\n<p>Based on 415V\/480V AC topologies with traditional UPS for short\u2011duration backup. Compute racks receive AC input and perform internal conversion to DC, leading to multiple efficiency bottlenecks. Capped at around 200kW per rack.<\/p>\n\n\n\n<p><strong>Stage 1: White Space Retrofit:<\/strong><\/p>\n\n\n\n<p>Introduces 800V DC racks while preserving existing AC infrastructure. An AC\/DC &#8216;Sidecar&#8217; unit in the white space handles the conversion. While this method enables high\u2011performance compute, it suffers from high cumulative conversion losses and consumes valuable floor space.<\/p>\n\n\n\n<p><strong>Stage 2: Hybrid Power Distribution:<\/strong><\/p>\n\n\n\n<p>Utilizes traditional transformers but introduces a DC UPS, connected in parallel to the 800V DC bus. During normal operation, power flows directly from source to load without passing through energy storage. This eliminates the 5\u20138% continuous loss of double\u2011conversion AC UPS systems. This stage begins to streamline the power path but retains the complexity and footprint of legacy AC components.<\/p>\n\n\n\n<p><strong>Stage 3: Basic DC<\/strong><strong>\u2011Native:<\/strong><\/p>\n\n\n\n<p>The first truly DC\u2011native configuration. A Solid State Transformer (SST) connects to MV and replaces the AC\/DC conversion stage. While this significantly improves efficiency and allows a parallel DC\u2011UPS to provide both backup power and active peak shaving, the architecture often relies on additional hardware. A step\u2011down transformer is frequently required to bridge higher grid voltages (typically up to 34.5\u202fkV) to the SST\u2019s working voltage, and separate low\u2011voltage (LV) distribution units are sometimes necessary. In this configuration, SST efficiency typically peaks at 98.5%<a href=\"#_ftn5\" id=\"_ftnref5\">[5]<\/a>.<\/p>\n\n\n\n<p><strong>Stage 4: Integrated DC<\/strong><strong>\u2011Native:<\/strong><\/p>\n\n\n\n<p>A high\u2011efficiency SST (&gt;99%) connects directly to 34.5\u202fkV AC and integrates DC distribution and native DC\u2011UPS capabilities into a single platform. By eliminating the need for intermediate step\u2011down transformers and separate LV distribution units, this fully integrated system provides seamless, granular power control and ultra\u2011fast response to both load demands and grid fluctuations.<\/p>\n\n\n\n<p><strong>SolarEdge data centre power solution<\/strong><\/p>\n\n\n\n<p>Building on 20 years of DC power electronics expertise, including six years of dedicated MV SST development, SolarEdge is engineering its core scientific breakthroughs into a holistic power platform for AI data centers. The design of the solution is intended to include the following key components:<\/p>\n\n\n\n<ol class=\"wp-block-list\">\n<li><strong>Ultra<\/strong><strong>\u2011High Efficiency SST (&gt;99%)<\/strong>: the Solid State Transformer will aim to interface directly with up to 34.5\u202fkV MV lines, delivering stabilized 800\u202fV\u20131500\u202fV DC to the racks, minimizing conversion losses to unlock more revenue\u2011generating compute.<\/li>\n\n\n\n<li><strong>Native DC<\/strong><strong>\u2011UPS<\/strong>: will aim to connect to the DC bus, eliminating AC\u2011DC\u2011AC conversions for maximal efficiency with seamless backup and peak shaving. Highly flexible, it is designed to allow independent, per\u2011deployment configuration of battery chemistry, capacity, and physical placement.<\/li>\n\n\n\n<li><strong>Integrated Intelligent Distribution<\/strong>: this smart DC\u2011power layer will aim to actively manage power delivery by combining per\u2011channel monitoring with localised control. It will aim to dynamically adapt to varying loads while ensuring enhanced safety, including rapid fault isolation.<\/li>\n<\/ol>\n\n\n\n<p>According to the maturity framework, the SolarEdge solution is intended to represent a Stage 4 architecture. By combining high\u2011efficiency SST technology with integrated DC distribution and a native DC\u2011UPS, the system aims to achieve state\u2011of\u2011the\u2011art total efficiency while meeting the extreme response\u2011time requirements of modern AI workloads.<\/p>\n\n\n\n<p>The following section examines SolarEdge Solid State Transformer \u2013 the cornerstone of this platform. Subsequent documentation will explore other system components as well as critical design considerations for the next generation of power\u2011dense data centres.<\/p>\n\n\n\n<p>SolarEdge SST intends to address the extreme needs of AI workloads, including:<\/p>\n\n\n\n<ol start=\"1\" class=\"wp-block-list\">\n<li><strong>Operating efficiency exceeding 99%<\/strong>: with efficiency well above current industry benchmarks, the SST aims to minimise conversion losses and subsequent cooling requirements. By reclaiming power that was previously lost to conversion and cooling, operators will be able to deploy additional compute within the same utility or on\u2011site generation envelope \u2013 transforming efficiency into a direct revenue driver.<\/li>\n\n\n\n<li><strong>Comprehensive Grid Support<\/strong>: providing ultra\u2011fast response to grid transients. The SST will be designed to perform active harmonic filtering, ensuring superior power quality and grid compliance without the need for external hardware.<\/li>\n\n\n\n<li><strong>Modular, scalable design<\/strong>: delivered in 2\u20135MW modular units with cell\u2011level redundancy, the design eliminates single points of failure at both the component and system levels to ensure maximum uptime.<\/li>\n\n\n\n<li><strong>Flexible and future proof<\/strong>: the SST platform is designed to support Medium Voltage (MV) inputs up to 34.5kV and pre\u2011configured DC outputs from 800V to 1500V (and could also support OCP\u2019s \u00b1400\u202fV), in line with current designs and future high\u2011voltage industry roadmaps.<\/li>\n<\/ol>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-full\"><a href=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-2.png\"><img loading=\"lazy\" decoding=\"async\" width=\"602\" height=\"237\" src=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-2.png\" alt=\"\" class=\"wp-image-31656\" srcset=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-2.png 602w, https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image-2-300x118.png 300w\" sizes=\"auto, (max-width: 602px) 100vw, 602px\" \/><\/a><figcaption class=\"wp-element-caption\">SolarEdge solid state transformer<\/figcaption><\/figure>\n<\/div>\n\n\n<p><strong>The DC expertise AI data centres need<\/strong><\/p>\n\n\n\n<p>The transition to 800V DC architecture in AI data centres requires unique expertise in DC power system design and management. With 20 years of leadership in DC power electronics, SolarEdge is positioned to seamlessly bridge this gap. Technologies perfected for distributed energy systems \u2013 such as granular power tracking, advanced string management, and rapid arc\u2011fault detection \u2013 translate naturally into the rigorous rack\u2011level power control and safety protocols demanded by high\u2011density AI workloads.<\/p>\n\n\n\n<p>Beyond advanced engineering, securing AI power infrastructure requires deep system visibility and massive operational capacity. Drawing on experience from the real\u2011time monitoring of millions of DC\u2011coupled systems across more than 140\u202fmillion units worldwide, the SST platform is engineered specifically to meet the stringent uptime targets of modern data centers. As these facilities reach gigawatt scale, proven manufacturing execution becomes critical. Leveraging a resilient supply chain and a track record of 60\u202fGW+ in globally deployed power electronics, SolarEdge is positioned to deliver this 800V DC infrastructure at scale and on time.<\/p>\n\n\n\n<p>Dafna Granot, Meir Adest and Igor Morozov are with <strong><a href=\"https:\/\/www.solaredge.com\/uk\/\" type=\"link\" id=\"https:\/\/www.solaredge.com\/uk\/\">SolarEdge<\/a><\/strong>.<\/p>\n\n\n\n<p><a href=\"#_ftnref1\" id=\"_ftn1\">[1]<\/a> Nvidia, Energy for tokens: thermal and power innovations, 20<\/p>\n\n\n\n<p><a href=\"#_ftnref2\" id=\"_ftn2\">[2]<\/a> McKinsey Data Center Demand Model, 2024<\/p>\n\n\n\n<p><a href=\"#_ftnref3\" id=\"_ftn3\">[3]<\/a> Inspired by the framework presented in Nvidia\u2019s paper: \u201c800 VDC Architecture for Next-Generation AI Infrastructure\u201d, 2025, with additional refinement of the DC-native solution.<\/p>\n\n\n\n<p><a href=\"#_ftnref4\" id=\"_ftn4\">[4]<\/a> All system efficiencies measured from 34.5kV MV grid to 54V DC compute tray bus. VRMs and cooling overhead excluded as they are consistent across architectures.<\/p>\n\n\n\n<p><a href=\"#_ftnref5\" id=\"_ftn5\">[5]<\/a> According to commercially announced SST products from leading vendors, as of Q1 2026<\/p>\n","protected":false},"excerpt":{"rendered":"<p>With more than 100GW of new AI data centre capacity expected between 2026 and 2030, operators are discovering that traditional AC energy infrastructure can&#8217;t scale alongside megawatt\u2011class GPU racks. In AC power chains, 10-30% of all incoming energy is lost as heat before it ever reaches a GPU, an inefficiency many operators now call the&nbsp;conversion &hellip;<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[199,107],"tags":[353,14615,14614],"class_list":["post-31653","post","type-post","status-publish","format-standard","","category-news-views-and-opinion","category-power","tag-ai","tag-solaredge","tag-solaredge-data-center-power-solution"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.4 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>How solid-state transformers and DCNative architecture aim to define the next generation of AI factories - Engineer News Network<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories - Engineer News Network\" \/>\n<meta property=\"og:description\" content=\"With more than 100GW of new AI data centre capacity expected between 2026 and 2030, operators are discovering that traditional AC energy infrastructure can&#8217;t scale alongside megawatt\u2011class GPU racks. In AC power chains, 10-30% of all incoming energy is lost as heat before it ever reaches a GPU, an inefficiency many operators now call the&nbsp;conversion &hellip;\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/\" \/>\n<meta property=\"og:site_name\" content=\"Engineer News Network\" \/>\n<meta property=\"article:published_time\" content=\"2026-03-24T09:45:00+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-03-24T14:48:34+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png\" \/>\n\t<meta property=\"og:image:width\" content=\"602\" \/>\n\t<meta property=\"og:image:height\" content=\"245\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"admin\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"admin\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"9 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/\"},\"author\":{\"name\":\"admin\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#\\\/schema\\\/person\\\/4477342aea8e299c6a21761e513ea8e1\"},\"headline\":\"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories\",\"datePublished\":\"2026-03-24T09:45:00+00:00\",\"dateModified\":\"2026-03-24T14:48:34+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/\"},\"wordCount\":1876,\"image\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/image.png\",\"keywords\":[\"AI\",\"SolarEdge\",\"SolarEdge data center power solution\"],\"articleSection\":[\"News, Views and Opinion\",\"Power\"],\"inLanguage\":\"en-GB\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/\",\"name\":\"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories - Engineer News Network\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/image.png\",\"datePublished\":\"2026-03-24T09:45:00+00:00\",\"dateModified\":\"2026-03-24T14:48:34+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#\\\/schema\\\/person\\\/4477342aea8e299c6a21761e513ea8e1\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/image.png\",\"contentUrl\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/image.png\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#website\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/\",\"name\":\"Engineer News Network\",\"description\":\"The ultimate online news and information resource for today's engineer\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#\\\/schema\\\/person\\\/4477342aea8e299c6a21761e513ea8e1\",\"name\":\"admin\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories - Engineer News Network","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/","og_locale":"en_GB","og_type":"article","og_title":"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories - Engineer News Network","og_description":"With more than 100GW of new AI data centre capacity expected between 2026 and 2030, operators are discovering that traditional AC energy infrastructure can&#8217;t scale alongside megawatt\u2011class GPU racks. In AC power chains, 10-30% of all incoming energy is lost as heat before it ever reaches a GPU, an inefficiency many operators now call the&nbsp;conversion &hellip;","og_url":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/","og_site_name":"Engineer News Network","article_published_time":"2026-03-24T09:45:00+00:00","article_modified_time":"2026-03-24T14:48:34+00:00","og_image":[{"width":602,"height":245,"url":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png","type":"image\/png"}],"author":"admin","twitter_card":"summary_large_image","twitter_misc":{"Written by":"admin","Estimated reading time":"9 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#article","isPartOf":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/"},"author":{"name":"admin","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1"},"headline":"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories","datePublished":"2026-03-24T09:45:00+00:00","dateModified":"2026-03-24T14:48:34+00:00","mainEntityOfPage":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/"},"wordCount":1876,"image":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#primaryimage"},"thumbnailUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png","keywords":["AI","SolarEdge","SolarEdge data center power solution"],"articleSection":["News, Views and Opinion","Power"],"inLanguage":"en-GB"},{"@type":"WebPage","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/","url":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/","name":"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories - Engineer News Network","isPartOf":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#primaryimage"},"image":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#primaryimage"},"thumbnailUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png","datePublished":"2026-03-24T09:45:00+00:00","dateModified":"2026-03-24T14:48:34+00:00","author":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1"},"breadcrumb":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/"]}]},{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#primaryimage","url":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png","contentUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/03\/image.png"},{"@type":"BreadcrumbList","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/how-solid-state-transformers-and-dcnative-architecture-aim-to-define-the-next-generation-of-ai-factories\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.engineernewsnetwork.com\/blog\/"},{"@type":"ListItem","position":2,"name":"How solid-state transformers and DCNative architecture aim to define the next generation of AI factories"}]},{"@type":"WebSite","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#website","url":"https:\/\/www.engineernewsnetwork.com\/blog\/","name":"Engineer News Network","description":"The ultimate online news and information resource for today's engineer","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.engineernewsnetwork.com\/blog\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Person","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1","name":"admin","url":"https:\/\/www.engineernewsnetwork.com\/blog\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/31653","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/comments?post=31653"}],"version-history":[{"count":5,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/31653\/revisions"}],"predecessor-version":[{"id":31697,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/31653\/revisions\/31697"}],"wp:attachment":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/media?parent=31653"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/categories?post=31653"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/tags?post=31653"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}