{"id":33648,"date":"2026-09-11T09:30:00","date_gmt":"2026-09-11T08:30:00","guid":{"rendered":"https:\/\/www.engineernewsnetwork.com\/blog\/?p=33648"},"modified":"2026-09-10T08:16:17","modified_gmt":"2026-09-10T07:16:17","slug":"immersion-cooling-and-dielectric-fluids-transforming-data-centres","status":"publish","type":"post","link":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/","title":{"rendered":"Immersion cooling and dielectric fluids transforming\u00a0data centres"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\"><strong>Immersion cooling with advanced dielectric fluids\u00a0is transforming\u00a0data centres, delivering dramatic energy savings, exceptional safety, and maintenance-free operation\u00a0for facilities seeking next-generation, sustainable cooling solutions. Eric Wong reports<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">As demand for data processing continues to climb, data centres are under pressure to increase performance while reducing energy use, maintenance costs, and environmental impact. In response, many operators are exploring alternative cooling technologies, and none have emerged as more promising than immersion cooling.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Unlike traditional air-cooled systems or even direct-to-chip liquid cooling, immersion cooling completely submerges servers directly into a dielectric fluid. This non-conductive, thermally stable liquid draws heat away from critical components such as CPUs and GPUs, efficiently transferring it to a secondary loop that rejects the heat outdoors via a cooling tower or fluid cooler. By eliminating air cooling entirely and improving thermal transfer efficiency, immersion cooling has the potential to radically reshape how data centres are operated.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">At the heart of this innovation is the dielectric fluid itself. This specialised fluid is what enables submersion cooling to work safely, affordably, and with minimal maintenance. This article explores what makes dielectric fluids so effective and why more data centres are turning to them \u2013 in conjunction with immersion cooling \u2013 as the future of sustainable and reliable cooling.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Understanding dielectric fluids<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Dielectric fluids are electrically non-conductive liquids with strong thermal transfer properties. Their ability to absorb and carry heat without conducting electricity makes them suitable for server immersion cooling, where they come into direct contact with server electronics. Common types of dielectric fluids include mineral oils, synthetic hydrocarbons, esters, and fluorocarbons. Each formulation has its advantages depending on application requirements, including temperature range, environmental impact, flammability, and material compatibility.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">For data centres, the most desirable fluids combine excellent heat transfer capabilities with long-term material stability, low environmental risk, and minimal fire hazard. These fluids require little to no regular replacement, as they do not evaporate or degrade easily, which offers long-term cost savings and operational simplicity.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Why dielectric fluids are a reliable choice<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A major concern for data center operators exploring immersion cooling is safety\u2014particularly the risk of leaks, equipment damage, or fire. Fortunately, dielectric fluids are specifically designed with these risks in mind.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Non-conductivity is their most critical safety feature. Even in the event of an unlikely leak or accidental spillage, dielectric fluids are non-toxic, non-corrosive, chemically inert, and biodegradable.&nbsp;<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Dielectric fluids can safely contact sensitive electronics and servers without causing equipment damage, unlike water based or glycol based coolants used in other systems.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Fire safety is another key advantage. Because many dielectric fluids are engineered to be fire-resistant and have low vapor pressures, they present a significantly lower fire risk than traditional air-cooled systems, which rely on high-speed fans and densely packed components.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In fact, well established chemical and oil companies have developed dielectric fluids with high flash points and low volatility, making them far less flammable than earlier generations of coolant oils.&nbsp;<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Efficiency that pays off<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">While switching to immersion cooling may seem like a major investment upfront, the long-term cost benefits of dielectric fluid systems are substantial. First, immersion cooling enables significantly higher heat transfer efficiency than air cooling. This leads to reduced reliance on energy-intensive chillers and HVAC systems.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">According to estimates from Schneider Electric and other industry sources, data centres using immersion cooling can reduce cooling energy consumption by up to 90%. This translates into a major reduction in operating costs, especially as energy prices rise and sustainability goals become more aggressive.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Furthermore, dielectric fluids have long service lives. Many dielectric fluids on the market today are engineered to remain effective for 10 years or more with minimal degradation. That longevity dramatically reduces the total cost of ownership (TCO), especially when compared to fluids that require regular draining, filtering, or replacement. Because immersion systems also eliminate the need for air handling units, raised floors, and other infrastructure associated with traditional cooling methods, capital expenditures can be redirected to more efficient designs.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">One of the most attractive features of dielectric fluid immersion systems is how little maintenance they require. Traditional air-cooled systems demand regular filter changes, fan inspections, airflow monitoring, and cleaning to prevent dust accumulation. In contrast, immersion cooling systems are largely self-contained. The closed-loop environment of the dielectric fluid bath protects internal components from contaminants like dust and debris, significantly extending equipment lifespan while reducing the need for cleaning.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Because of the fluid&#8217;s stability and resistance to evaporation, dielectric coolant levels stay consistent over time, further simplifying operations. There are fewer mechanical parts to service, fewer failure points, and fewer emergencies that require downtime or technician intervention.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">For facilities with limited IT support staff or a desire to reduce maintenance workloads, immersion cooling using dielectric fluid provides a highly appealing path forward.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Promoting a future-ready cooling strategy<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Immersion cooling with dielectric fluids also supports growing sustainability and ESG initiatives. Many fluids are biodegradable and designed with low toxicity profiles, reducing environmental impact both during use and at end-of-life disposal. The improved thermal efficiency of these systems also means less energy is used for cooling, resulting in lower greenhouse gas emissions. Some systems can also be paired with heat reuse infrastructure, repurposing waste heat for building heating or other applications\u2014further enhancing their sustainability. Additionally, the reduced need for air handlers and HVAC equipment lowers the embodied carbon of data center construction and enables more compact facility footprints.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">While many cooling strategies will continue to coexist depending on workload, climate, and facility type, immersion cooling represents a forward-looking solution that addresses key challenges across the board: heat density, operational efficiency, cost control, and environmental impact. The choice of dielectric fluid plays a central role in realising these benefits. From synthetic esters to engineered hydrocarbons, modern dielectric fluids provide the safety, stability, and performance necessary to support long-term immersion cooling deployments.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Eric Wong is Product Marketing Engineer at<strong> <a href=\"https:\/\/baltimoreaircoil.com\/\" target=\"_blank\" rel=\"noopener\">Baltimore\u00a0Aircoil Company (BAC)<\/a><\/strong>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Immersion cooling with advanced dielectric fluids\u00a0is transforming\u00a0data centres, delivering dramatic energy savings, exceptional safety, and maintenance-free operation\u00a0for facilities seeking next-generation, sustainable cooling solutions. Eric Wong reports As demand for data processing continues to climb, data centres are under pressure to increase performance while reducing energy use, maintenance costs, and environmental impact. In response, many operators &hellip;<\/p>\n","protected":false},"author":1,"featured_media":33649,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[199,1],"tags":[15532,15534,15533,14517],"class_list":["post-33648","post","type-post","status-publish","format-standard","has-post-thumbnail","","category-news-views-and-opinion","category-process","tag-bac-2","tag-data-centrres","tag-dielectric-fluids","tag-immersion-cooling"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.4 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Immersion cooling and dielectric fluids transforming\u00a0data centres - Engineer News Network<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Immersion cooling and dielectric fluids transforming\u00a0data centres - Engineer News Network\" \/>\n<meta property=\"og:description\" content=\"Immersion cooling with advanced dielectric fluids\u00a0is transforming\u00a0data centres, delivering dramatic energy savings, exceptional safety, and maintenance-free operation\u00a0for facilities seeking next-generation, sustainable cooling solutions. Eric Wong reports As demand for data processing continues to climb, data centres are under pressure to increase performance while reducing energy use, maintenance costs, and environmental impact. In response, many operators &hellip;\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/\" \/>\n<meta property=\"og:site_name\" content=\"Engineer News Network\" \/>\n<meta property=\"article:published_time\" content=\"2026-09-11T08:30:00+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/09\/BAC-Immersion-Cooling-2-1-scaled.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"2560\" \/>\n\t<meta property=\"og:image:height\" content=\"1919\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"admin\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"admin\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"5 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/\"},\"author\":{\"name\":\"admin\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#\\\/schema\\\/person\\\/4477342aea8e299c6a21761e513ea8e1\"},\"headline\":\"Immersion cooling and dielectric fluids transforming\u00a0data centres\",\"datePublished\":\"2026-09-11T08:30:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/\"},\"wordCount\":986,\"image\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/09\\\/BAC-Immersion-Cooling-2-1-scaled.jpg\",\"keywords\":[\"BAC\",\"data centrres\",\"Dielectric Fluids\",\"immersion cooling\"],\"articleSection\":[\"News, Views and Opinion\",\"Process\"],\"inLanguage\":\"en-GB\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/\",\"name\":\"Immersion cooling and dielectric fluids transforming\u00a0data centres - Engineer News Network\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/09\\\/BAC-Immersion-Cooling-2-1-scaled.jpg\",\"datePublished\":\"2026-09-11T08:30:00+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#\\\/schema\\\/person\\\/4477342aea8e299c6a21761e513ea8e1\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/09\\\/BAC-Immersion-Cooling-2-1-scaled.jpg\",\"contentUrl\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/09\\\/BAC-Immersion-Cooling-2-1-scaled.jpg\",\"width\":2560,\"height\":1919,\"caption\":\"Dielectric fluids can safely contact sensitive electronics and servers without causing equipment damage\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Immersion cooling and dielectric fluids transforming\u00a0data centres\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#website\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/\",\"name\":\"Engineer News Network\",\"description\":\"The ultimate online news and information resource for today's engineer\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/#\\\/schema\\\/person\\\/4477342aea8e299c6a21761e513ea8e1\",\"name\":\"admin\",\"url\":\"https:\\\/\\\/www.engineernewsnetwork.com\\\/blog\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Immersion cooling and dielectric fluids transforming\u00a0data centres - Engineer News Network","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/","og_locale":"en_GB","og_type":"article","og_title":"Immersion cooling and dielectric fluids transforming\u00a0data centres - Engineer News Network","og_description":"Immersion cooling with advanced dielectric fluids\u00a0is transforming\u00a0data centres, delivering dramatic energy savings, exceptional safety, and maintenance-free operation\u00a0for facilities seeking next-generation, sustainable cooling solutions. Eric Wong reports As demand for data processing continues to climb, data centres are under pressure to increase performance while reducing energy use, maintenance costs, and environmental impact. In response, many operators &hellip;","og_url":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/","og_site_name":"Engineer News Network","article_published_time":"2026-09-11T08:30:00+00:00","og_image":[{"width":2560,"height":1919,"url":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/09\/BAC-Immersion-Cooling-2-1-scaled.jpg","type":"image\/jpeg"}],"author":"admin","twitter_card":"summary_large_image","twitter_misc":{"Written by":"admin","Estimated reading time":"5 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#article","isPartOf":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/"},"author":{"name":"admin","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1"},"headline":"Immersion cooling and dielectric fluids transforming\u00a0data centres","datePublished":"2026-09-11T08:30:00+00:00","mainEntityOfPage":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/"},"wordCount":986,"image":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#primaryimage"},"thumbnailUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/09\/BAC-Immersion-Cooling-2-1-scaled.jpg","keywords":["BAC","data centrres","Dielectric Fluids","immersion cooling"],"articleSection":["News, Views and Opinion","Process"],"inLanguage":"en-GB"},{"@type":"WebPage","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/","url":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/","name":"Immersion cooling and dielectric fluids transforming\u00a0data centres - Engineer News Network","isPartOf":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#primaryimage"},"image":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#primaryimage"},"thumbnailUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/09\/BAC-Immersion-Cooling-2-1-scaled.jpg","datePublished":"2026-09-11T08:30:00+00:00","author":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1"},"breadcrumb":{"@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/"]}]},{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#primaryimage","url":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/09\/BAC-Immersion-Cooling-2-1-scaled.jpg","contentUrl":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-content\/uploads\/2026\/09\/BAC-Immersion-Cooling-2-1-scaled.jpg","width":2560,"height":1919,"caption":"Dielectric fluids can safely contact sensitive electronics and servers without causing equipment damage"},{"@type":"BreadcrumbList","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/immersion-cooling-and-dielectric-fluids-transforming-data-centres\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.engineernewsnetwork.com\/blog\/"},{"@type":"ListItem","position":2,"name":"Immersion cooling and dielectric fluids transforming\u00a0data centres"}]},{"@type":"WebSite","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#website","url":"https:\/\/www.engineernewsnetwork.com\/blog\/","name":"Engineer News Network","description":"The ultimate online news and information resource for today's engineer","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.engineernewsnetwork.com\/blog\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Person","@id":"https:\/\/www.engineernewsnetwork.com\/blog\/#\/schema\/person\/4477342aea8e299c6a21761e513ea8e1","name":"admin","url":"https:\/\/www.engineernewsnetwork.com\/blog\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/33648","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/comments?post=33648"}],"version-history":[{"count":1,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/33648\/revisions"}],"predecessor-version":[{"id":33650,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/posts\/33648\/revisions\/33650"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/media\/33649"}],"wp:attachment":[{"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/media?parent=33648"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/categories?post=33648"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.engineernewsnetwork.com\/blog\/wp-json\/wp\/v2\/tags?post=33648"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}